论文部分内容阅读
对应用于南海意库3#办公楼的温湿度独立控制空调系统进行了实际运行测试与实践,结果表明溶液除湿新风机组承担了室内全部潜热负荷以及人员的显热负荷,室内空气温度约为25~26℃、相对湿度约为50%~60%,且干式风机盘管在整个供冷季保持干工况运行。新风机组宜提前1.5~2h开机对室内除湿,高温冷水机组宜提前1~1.5h开机除去室内显热负荷。
The actual operation test and practice of temperature and humidity independent control air-conditioning system applied to Office Building 3 # in South China Sea are shown. The results show that the solution dehumidification fresh air unit undertakes the indoor total latent heat load and the sensible heat load of personnel, and the indoor air temperature is about 25 ~ 26 ℃, relative humidity is about 50% ~ 60%, and dry fan coil to maintain dry conditions throughout the cooling season. Fresh air unit should be 1.5 ~ 2h boot in advance indoor dehumidification, high temperature chiller should be boot 1 ~ 1.5h in advance to remove the indoor sensible heat load.