介绍了适合于车辆空调热膨胀阀(TXV)的嘶嘶声和流动声的测试方法。嘶嘶声测试系统包括人工头、麦克风和加速度传感器,它可以采集噪声和振动信号,并通过观察窗来评估流过位于TXV前部的液体管里的冷凝剂的质量。测试表明,嘶嘶声的根本原因是制冷剂没有完全冷凝成液态,致使气体和液体的混合物进入TXV,混合物的膨胀产生嘶嘶声。若制冷剂是以液体形式进入热膨胀阀,嘶嘶声基本就听不到了。TXV的设计(文章中没有涉及)和蒸发器的隔离均对嘶嘶声有影响。此外还采用本文所提出的测试方法进行了实际测试和原因分析。
A test method for hissing and flowing sound suitable for vehicle air conditioning thermal expansion valve (TXV) is introduced. The hissing test system consists of an artificial head, a microphone and an accelerometer, which collect noise and vibration signals and evaluate the quality of the condensate flowing through the liquid tube located in the front of the TXV through the sight glass. Tests have shown that the fundamental cause of hissing is that the refrigerant does not completely condense into a liquid state, causing the mixture of gas and liquid to enter the TXV and the mixture to expand to create a hissing sound. If the refrigerant is in the form of liquid into the thermal expansion valve, the hiss basically can not hear. The design of the TXV (not covered in the article) and the isolation of the evaporator have an impact on the hiss. In addition, the test method proposed in this paper has been used to conduct actual tests and analysis of causes.